The CM4373-50 is a 2000 A True RMS clamp meter that features stronger jaws, IP54 dustproof and waterproof enclosure to enable professionals to work quickly in tough situations including the development, repair, and maintenance of equipment and devices such as electric vehicles.
- DC High V Probe Mode enables high voltage measurement up to CAT III 2000 V
- When the Wireless Adapter Z3210 is installed, Bluetooth wireless communication is enabled
- When combined with GENNECT Cross, you can perform simple harmonic analysis
- Convenient for repeated measurement and recording tasks with automatic hold function
- Assess transient currents at motor startup
| DC Current range | 600.0 A/2000 A, Basic accuracy: ±1.3% rdg. ±0.3 A (600 A range) |
|---|---|
| AC Current range | 600.0 A/2000 A (10 Hz to 1 kHz, True RMS), Basic accuracy 45 - 66 Hz: ±1.3% rdg. ±0.3 A (at 600 A) |
| Crest factor | 600.0 A range: 3 or less 2000 A range: 2.84 or less |
| DC+AC Current range | 600.0 A/2000 A (10 Hz to 1 kHz, True RMS), Basic accuracy DC, 45-66 Hz: ±1.3% rdg. ±1.3 A (at 600 A) |
| DC Voltage range | 600.0 mV to 1000 V (When using P2000: 600.0 V to 2000 V) |
| AC Voltage range | 6.000 V to 1000 V, 4 ranges (15 Hz to 1 kHz, True RMS), Basic accuracy 45 - 66 Hz: ±0.9% rdg. ±0.003 V (at 6 V) |
| DC+AC Voltage range | 6.000 V to 1000 V, 4 ranges, Basic accuracy DC, 45 - 66 Hz: ±1.0% rdg. ±0.013 V (at 6 V) |
| Resistance range | 600.0 Ω to 6.000 MΩ, 5 ranges, Basic accuracy: ±0.7% rdg. ±0.5 Ω (at 600 Ω) |
| Capacitance range | 1.000 μF to 1000 μF, 4 ranges, Basic accuracy: ±1.9% rdg. ±0.005 μF (at 1 μF) |
| Frequency range | 9.999 Hz to 999.9 Hz, 3 ranges, Basic accuracy: ±0.1% rdg. ±0.003 Hz (at 9.999 Hz) |
| Temperature (K) | -40.0 to 400.0 ˚C, add temperature probe accuracy to basic accuracy of ±0.5% rdg. ±3.0 ˚C |
| Voltage detection | Hi: 40 V to 600 V AC, Lo: 80 V to 600 V AC, 50/60 Hz |
| Harmonic levels | [With Z3210 installed] Voltage/Current harmonic levels up to 30th, Content factor, Total harmonic distortion ratio *Harmonics can be displayed with our free app GENNECT Cross. |
| Other functions | DC power, Continuity check, Diode check, Automatic AC/DC detection, Pass/fail judgement function of DC A and DC V, Max/Min/Average/PEAK MAX/ PEAK MIN value display, Low-pass filter function, Display value hold, Auto hold, Back light, Auto-power save, Buzzer sounds, Zero-adjustment, etc. |
| Dustproof, waterproof | IP20 (Voltage measurement in a completely dry condition. When jaw closes) IP54 (While in storage) |
| Power supply | LR03 Alkaline battery ×2 Continuous use: 40 hr (without Z3210 installed), 24 hr. (with Z3210 installed and using wireless communications) Other conditions: 100 A AC measurement, backlight off, 23°C reference value |
| Core jaw diameter | φ55 mm (2.17 in), Jaw dimension: 92 mm (3.62 in) W×18 mm (0.71 in) D |
| Dimensions and mass | 65 mm (2.56 in) W×250 mm (9.84 in) H×35 mm (1.38 in) D mm, 530 g (18.7 oz) |
| Included accessories | Test Lead L9300, Carrying Case C0203, LR03 Alkaline battery ×2, Instruction Manual×2, Operating Precautions ×1 |
| Crest factor | 600.0 A range: 3 or less; 2000 A range: 2.84 or less |